Controller Menu – continued
Controller setup - continued -
6. Use the three controller buttons to activate the controller. An activated controller is
visually indicated in the menu Controller.
7. Use button Off to de-activate the controller.
8. If no controller type has been selected, the status indicator indicates Off. If a control-
ler has been selected, the respective button is highlighted in yellow and the status
indicator indicates On.
9. To configure the controller press button Continuous controller, button 2-pos. con-
troller or button 3-pos. controller.
Continuous controller setup
1. Press button Continuous controller in the menu Controller Setup.
2. The name of the controller is highlighted in
yellow.
3. The green input field Actual value shows
the actual value. Click in the input field to
show all established signals.
4. Select the signal that indicates the re-
quired parameters. For more information
on the setup and configuration of the
equipment see menu CAN Input and Ana-
log Input.
5. The green input field Setpoint shows the
setpoint element. The setpoint can be adjusted directly in the equipment or external-
ly, e. g. via a potentiometer.
6. To toggle between internal and external setpoint press button Internal setpoint/ Ex-
ternal setpoint.
7. To enter the signal for an external setpoint click in the green input field. All estab-
lished sensing elements will be indicated.
8. Select the signal that indicates the required parameters. For more information on the
setup and configuration of the equipment see menu CAN Input and Analog Input.
9. The green input field Manip. variable shows the manipulated variable element. To
select a signal for the manipulated variable click in the green input field. All adjusted
signals will be indicated.
10. Select the signal to which the manipulated variable shall be sent.
You will find the settings in the menu Analog Outputs.
Continuous
controller setup
Logo
MAX limit
Offset MIN limit
NC
NC
NC
NC
Position
Manip. variable
Actual value
Controller 1
Int. setpoint