GENERAL INFORMATIONThis bulletin is designed to assist in installing, calibrating,troubleshooting and performing maintenance as required for theXL90 S
1 Base assembly2 Cover3 Screw6 Pressure gauge 0-160 psi7 Bottom relay assembly8 O-ring9 Upper relay assembly10 Orifice screw11 O-ring12 O-ring13 Relay
1 Base assembly2 Cover3 Screw6 Pressure gauge 0-160 psi7 Bottom relay assembly8 O-ring9 Upper relay assembly10 Orifice screw11 O-ring12 O-ring13 Relay
XL90 Part Numbering SystemPREFIXSelection CodeAutomax Manufacture - Black Epoxy MBAutomax Manufacture - White Food Grade Epoxy MWAccord Manufacture -
General Spare Parts KitsStandard O-ring Kit – Part No. 10094526Item No. Description Quantity8 Relay/base O-ring and relay tube O-ring 611 Orifice scre
48-14 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611Shaft Kit, NAMUR End Connection – Part No. 10118753Item No. Description Qua
Transmitter Kit, 4-20mA Output, NAMUR Shaft EndConnection – Part No. 10118427Item No. Description Quantity52 Cam Shaft 1112 Retaining Ring 2128 Jam Nu
48-16 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611Intrinsically Safe Proximity Limit Switch Kit, NAMUR ShaftEnd Connection –
Supply air biases the pilot-valve in an upward direction. Asthe capsule moves up, it will close the exhaust seat of the upperpilot poppet and open the
Mounting Instructions for XL90 with NAMUR ShaftConnection1. Mount the bracket to the actuator. Finger tighten thebracket bolting. 2. If required, inst
3. Place cam over the shaft with the appropriate characteristicfacing up and closest to the span arm roller. For Seregcams, see Table I. For Accord ca
4. Remove rubber cap over balance adjustment screw. (SeeFigure 6.)5. Apply full actuator operating pressure to positioner supplyport.6. Set input sign
WARNING: Be certain power to I/P module is disconnectedbefore removing housing cover in explosive atmospheres;otherwise personal injury may occur.3. B
2. Remove the I/P module housing cover.WARNING: Be certain power to the I/P module is discon-nected before removing the housing cover in explosiveatmo
adjustable gain lower plate (26), and diaphragm plate.Remove signal diaphragm assembly (15) and remove relayplate (14) from between the diaphragms. Pl
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611 48-9Failure Probable Cause Corrective ActionValve won’t 1. Tubing to wrong port