Basic Settings – continued –
Establishing switchpoints and proportional coefficient X
p
Press button once briefly to activate
the line editing mode.
Use button or to scroll back and
forth through the lines
The split-screen main window shows
which GESTRA bus devices can be
indicated:
High-level limiter NRS 1-41
Low-level limiter NRS 1-40
Level switch NRS 2-40
Level controller NRR 2-40
Conductivity electrode LRR 1-40
Before commissioning the installation
establish proportional band and the M
AX/
M
IN switchpoints for the level controller
NRR 2-40.
For level switch NRS 2-40 you can
establish four switchpoints.
Press button three times briefly to enter
the window where you can establish the
switchpoints and the X
p
value.
3 times briefly
once briefly