14
The measuring range can be switch selected between 0.5 µS/cm and 10 µS/cm
by means of code switch :
1. Unscrew screws at the electrode terminal, remove cover , Fig. 6
DIP switch 1 4 OFF Measuring range
0.5 µS/cm.
DIP switch 1 4 ON Measuring range
10 µS/cm.
2. Replace cover and fasten screws .
Standard setting
Factory setting
The compact system is delivered with the following factory settings:
Measuring range 10 µS/cm
Switch selection of measuring range
Attention
Screwdriver for cross head screws, size 1
Screwdriver for slotted screws, size 2.5; completely insulated according
to VDE 0680
Do not damage the electronic components when setting the code
switch.