8 DDC-100 Direct-to-Host Programming Guide FCD LMAIM4019-00 FCD LMAIM4019-00 DDC-100 Direct-to-Host Programming Guide 9
Table 3.3 – DDC-100 Coil Assignments, Modbus Function Code 01 Usage for Digital Outputs
Coil
Number
Bit
Number
MX/DDC UEC-3-DDC DDC-100 Clamshell I/O Module
1 00 Close / Stop Close / Stop Close / Stop Do Not Use
2 01 Open / Stop Open / Stop Close / Stop Do Not Use
3 02 AS-1 Lockout or Relay #3 Lockout or Relay #3 Relay #3
4 03 AS-2 Do Not Use Relay #4 Relay #4
5 04 AS-3 Do Not Use Relay #5 Relay #5
6 05 AS-4 Relay #6 Relay #6 Relay #6
7 06 AR-1 (Opt) Do Not Use Do Not Use Relay #21
8 07 AR-2 (Opt) Do Not Use Do Not Use Relay #12
9 08 AR-3 (Opt) Do Not Use Do Not Use Do Not Use
Note 1: Relay #2 is physical Relay K2.
Note 2: Relay #1 is physical Relay K1.
Example
Poll field unit number 3 for 8 coils starting at coil 1.
Query 0301000000083C2E
Response 03010118503A
Message Breakdown
Query Response
03 Slave (Field Unit) Address 03
Slave (Field Unit)
Address
01 Function 01 Function
00 Starting Address Hi 01 Byte Count
00 Starting Address Lo 18 1 Data (Coils 8 - 1)
00 No. of Points Hi 503A Error Check (CRC)
08 No. of Points Lo
3C2E Error Check (CRC)
Note 1: 18h equals 00011000 or coils 4 and 5 are ON.
3.2.2 Modbus Function Code 02 (Read Input Status)
This function code is used to read the discrete input status bits in the DDC-100 Field Unit. The use
of this function code will provide the user with the input status bits that are used to develop holding
registers 9 through 13. The status bit inputs are contained in locations 10129-10208 for each
DDC-100 Field Unit and are defined in Table 3.4.
Table 3.4 – Status Bit Definitions
Bit Number
Modbus
Bit
Address
UEC-3-DDC and DDC-100 Clamshell I/O Module
129 128 Opened Not Used
130 129 Closed Not Used
131 130 Stopped Not Used
132 131 Opening Not Used
133 132 Closing Not Used
134 133 Valve jammed Not Used
135 134 Actuator switched to local mode Not Used
136 135 Combined fault Not Used
Table 3.4 – Status Bit Definitions (continued)
Bit Number
Modbus
Bit
Address
UEC-3-DDC and DDC-100 Clamshell I/O Module
137 136 Over-temperature fault Not Used
138 137 Actuator failing to de-energize Not Used
139 138 Channel A fault Channel A fault
140 139 Channel B fault Channel B fault
141 140 Open torque switch fault Not Used
142 141 Close torque switch fault Not Used
143 142 Valve operated manually fault Not Used
144 143 Phase error Not Used
145 144
Input “open verify” is not active after open
command is initiated
Not Used
146 145
Input “close verify” is not active after close
command is initiated
Not Used
147 146
Input “open verify” is active after open
command is de-energized
Not Used
148 147
Input “close verify” is active after close
command is de-energized
Not Used
149 148
“Ph_det” (Phase Detect) input is active.
One or more phases is missing
Not Used
150 149
“Ph_seq” (Phase Sequence) input is active.
Reverse phase sequence is occurring
Not Used
151 150
Valve manually moved from mid-travel to
open
Not Used
152 151
Valve manually moved from open to
mid-travel
Not Used
153 152
Valve manually moved from mid-travel to
close
154 153
Valve manually moved from close to
mid-travel
Not Used
155 154
Network emergency shutdown (ESD) is
active
Not Used
156 155 Local emergency shutdown is active Not Used
157 156
Field unit microprocessor has reset since
the last poll
Not Used
158 157 Wrong rotation Not Used
159 158 Opening in local mode Not Used
160 159 Closing in local mode Not Used
161 160 Close contactor (interlocked) Not Used
162 161 Open contactor (interlocked) Not Used
163 162 Lockout or user, Relay 3 Relay 3
164 163
Local pushbutton switch LED (UEC-3)
Relay 4 (Clamshell)
Relay 4
165 164
Local pushbutton switch LED (UEC-3)
Relay 5 (Clamshell)
Relay 5
166 165 User, Relay 6 Relay 6
167 166 Close contactor (non-interlocked) Relay 2 (K2)
168 167 Open contactor (non-interlocked) Relay 1 (K1)
169 168 Field unit software vs. ID Field unit software vs. ID
170 169 Field unit software vs. ID Field unit software vs. ID
171-176 170-175 Field unit software vs. ID Field unit software vs. ID
177 176 Remote switch User Input 8
178 177 Thermal overload User Input 9