Limitorque®DDC-100 Master Station IIInstallation and Operation ManualFCD LMAIM5001-00 (Replaces 435-11000)Limitorque Actuation Systems

Página 2

10 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 2-1: Screen flo

Página 3

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 11Flow Control DivisionLimitorque Actuation Systems3 Quick Startup3.1 Sin

Página 4

12 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems4. From the Main Menu

Página 5 - 1 Introduction

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 13Flow Control DivisionLimitorque Actuation Systems2. Press the screen of

Página 6

14 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 7 - 1.4 Main Menu

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 15Flow Control DivisionLimitorque Actuation Systems4 Connections4.1 Maste

Página 8

16 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 4-2: Debug Port

Página 9

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 17Flow Control DivisionLimitorque Actuation SystemsTable 4-1: Network Cha

Página 10 - Limitorque Actuation Systems

18 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsBelden 3105A Specifica

Página 11 - 3 Quick Startup

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 19Flow Control DivisionLimitorque Actuation Systems4.3 Master Station Net

Página 12

2 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsMaster StationInstallat

Página 13

20 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 14

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 21Flow Control DivisionLimitorque Actuation Systems5 Configuration5.1 Log

Página 15 - 4 Connections

22 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 5-2: The Config

Página 16

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 23Flow Control DivisionLimitorque Actuation SystemsFigure 5-4: Saving Cha

Página 17

24 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems5.3 Change TagsEach MO

Página 18

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 25Flow Control DivisionLimitorque Actuation Systems8. Tag names are limi

Página 19 - MASTER STATION II

26 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 20

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 27Flow Control DivisionLimitorque Actuation Systems6 MOV Network Configur

Página 21 - 5 Configuration

28 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 6-3: The second

Página 22

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 29Flow Control DivisionLimitorque Actuation SystemsFigure 6-5: The Active

Página 23

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 3Flow Control DivisionLimitorque Actuation Systems

Página 24 - 5.3 Change Tags

30 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 25

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 31Flow Control DivisionLimitorque Actuation Systems7 DCS Port Configurati

Página 26

32 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 7-2: The DCS Po

Página 27 - 6 MOV Network Configuration

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 33Flow Control DivisionLimitorque Actuation SystemsFigure 7-4: RTS ON Del

Página 28

34 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 7-6: The Select

Página 29

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 35Flow Control DivisionLimitorque Actuation Systems03 —Read Holding Regis

Página 30

36 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsSelecting a register f

Página 31 - 7 DCS Port Configuration

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 37Flow Control DivisionLimitorque Actuation SystemsName MX-DDC UEC-3-DDCD

Página 32

38 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsDCS Requested Register

Página 33 - 7.2 Data Table Configuration

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 39Flow Control DivisionLimitorque Actuation SystemsFigure 7-10: The Data

Página 34 - MNET Status

4 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems

Página 35

40 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 7-11: The Write

Página 36

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 41Flow Control DivisionLimitorque Actuation SystemsValid Command Register

Página 37

42 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems02 —Read Input StatusR

Página 38

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 43Flow Control DivisionLimitorque Actuation Systems04 —Read Input Registe

Página 39

44 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 40

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 45Flow Control DivisionLimitorque Actuation Systems8 Ethernet Port Config

Página 41

46 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 8-3: Edit Octet

Página 42

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 47Flow Control DivisionLimitorque Actuation Systems9 General Settings Con

Página 43

48 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 9-2: The Config

Página 44

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 49Flow Control DivisionLimitorque Actuation SystemsFigure 9-4: The Change

Página 45 - Ethernet Port Configuration

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 5Flow Control DivisionLimitorque Actuation Systems1 Introduction1.1 Overv

Página 46

50 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems9.4 VersionThe Version

Página 47 - << Back

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 51Flow Control DivisionLimitorque Actuation Systems10 Hot Standby Configu

Página 48 - 1 / 1 / 2003 12 : 30

52 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsHot) and allows the us

Página 49

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 53Flow Control DivisionLimitorque Actuation Systems10.3 OperationUnder no

Página 50 - Master Station Revisions

54 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 51 - 10 Hot Standby Configuration

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 55Flow Control DivisionLimitorque Actuation Systems11 Network StatusThe N

Página 52

56 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 53 - 10.3 Operation

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 57Flow Control DivisionLimitorque Actuation Systems12 View MOV StatusThe

Página 54

58 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 12-3: View MOV

Página 55 - 11 Network Status

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 59Flow Control DivisionLimitorque Actuation SystemsPage 5 (Figure 12-5) p

Página 56

6 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems1.3 LoginWhen the Maste

Página 57 - 12 View MOV Status

60 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 58 - Status Info

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 61Flow Control DivisionLimitorque Actuation Systems13 Control MOVMOVs can

Página 59

62 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 13-3: Control A

Página 60

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 63Flow Control DivisionLimitorque Actuation Systems14 Emergency Shut Down

Página 61 - 13 Control MOV

64 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsWhen an Emergency Shut

Página 62

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 65Flow Control DivisionLimitorque Actuation Systems15 LoggerThe Logger al

Página 63 - 14 Emergency Shut Down

66 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 15-2: Data Anal

Página 64 - Procedure Complete

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 67Flow Control DivisionLimitorque Actuation SystemsFigure 15-4: Data Anal

Página 65 - 15 Logger

68 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 66

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 69Flow Control DivisionLimitorque Actuation Systems16 Error MessagesError

Página 67

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 7Flow Control DivisionLimitorque Actuation SystemsFigure 1-3: The Login H

Página 68

70 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 16-3: Configura

Página 69 - 16 Error Messages

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 71Flow Control DivisionLimitorque Actuation SystemsFigure 16-5: HMI Locko

Página 70

72 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 71

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 73Flow Control DivisionLimitorque Actuation Systems17 Web Server Operatio

Página 72

74 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 17-2Figure 17-3

Página 73 - 17 Web Server Operation

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 75Flow Control DivisionLimitorque Actuation SystemsFigure 17-4Key: = Red=

Página 74 - To be supplied

76 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsFigure 17-4Note: The s

Página 75

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 77Flow Control DivisionLimitorque Actuation SystemsFigure 17-4Note: Gray

Página 76

78 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intention

Página 77

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 79Flow Control DivisionLimitorque Actuation Systems18 Touch Panel Backlig

Página 78

8 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation SystemsThis page is intentiona

Página 79 - 18 Touch Panel Backlight

80 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Flow Control DivisionLimitorque Actuation Systems80 DDC-100 Master Stat

Página 80

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 81Flow Control DivisionLimitorque Actuation SystemsFCD LMAIM5001-00 DDC-1

Página 81

82 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00This page is intentionally blank.Flow Control DivisionLimitorque Actuat

Página 82

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 8320 How to Order PartsTo order parts or obtain further information about

Página 83 - 20 How to Order Parts

84 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00This page is intentionally blank.Flow Control DivisionLimitorque Actuat

Página 84

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 8521 AppendixFigure A-1: Typical single Master Station II network diagram

Página 85 - 21 Appendix

86 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00Figure A-2: Typical hot standby Master Station II network diagramLimito

Página 86

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 87Flow Control DivisionLimitorque Actuation Systems

Página 87

Flow Control DivisionLimitorque Actuation Systems Limitorque 5114 Woodall Road, P.O. Box 11318Lynchburg, VA 24506-1318Phone (434) 528-4400, Fax (434)

Página 88

FCD LMAIM5001-00 DDC-100 Master Station II Installation and Operation Manual 9Flow Control DivisionLimitorque Actuation Systems2 Master Station II Scr