Flowserve DDC-100 Master Station II Manual do Utilizador Página 76

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 88
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 75
76 DDC-100 Master Station II Installation and Operation Manual FCD LMAIM5001-00
Flow Control Division
Limitorque Actuation Systems
Figure 17-4
Note: The setting shown above indicates default.
Master Station Confi guration
DCS Port Setup
DCS Address 1
DCS Baud Rate 9600
DCS Stop 1
DCS Parity None
DCS Electrical RS-232
DCS RTS ON 0
DCS RTS OFF 0
DCS HB Start Hot
DCS HMI Enabled Disable
Ethernet Port Setup
Enet ReadWrite Read Only
IP Address 192.168.0.100
Mask 255.255.255.0
Gateway 192.168.0.1
Standby IP Address 0.0.0.0
DCS Port / Ethernet port Data Table Parameters
DCS Register First Position
DCS Register Last Status
DCS 5/15 Coil Map ‘Close / Stop’ through ‘Open / Stop’
DCS Write Register 1
Network Setup
Network Baud Rate 9600
Network Timeout 500
Network Retries 1
Network Poll Mode LOOP
Network Propogation Delay 10
Network RTS Delay 10
First Confi gured Slave 1
Last Confi gured Slave 32
Total Active Slaves 32
MOV Active/Inactive Status
MOV 001-032
MOV 033-064
MOV 065-096
MOV 097-128
MOV 129-160
MOV 161-192
MOV 193-224
MOV 225-250
Vista de página 75