10. Technical data
Common data
Repeatability <0,3%
Air delivery Supply at 600 kPa 125 nl/min
Air delivery Exhaust at 600 kPa 125 nl/min
Air supply pressure range 140-600kPa
Gain % / % acc. to ISA S75 5 to 30 %/%
Temperature range -40°C to +85°C
Temperature sensitivity < 0.4% per 10°C
Stroke length 6 - 60 mm, option 3 mm
Other data
P3
Linearity <±1%
Hysteresis + Deadband <0.5%
Deadband <0.15%
Air consumption (depending on gain setting) 2-8 nl/min
Supply pressure sensitivity <0.20%
Input signal 0.2 - 1 bar (3 - 15 psi)
EP3
Linearity <±1.5%
Hysteresis + Deadband <1%
Deadband <0.2%
Air consumption (depending on gain setting) 4-10 nl/min
Supply pressure sensitivity <0.3%
Input signal 4 - 20 mA
EP3EX
Linearity <±1.5%
Hysteresis + Deadband <1%
Deadband <0.2%
Air consumption (depending on gain setting) 4-10 nl/min
Supply pressure sensitivity <0.3%
Input signal 4 - 20 mA
Vista de página 19