Flowserve TRV5-40 Manual do Utilizador Página 17

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 28
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 16
17
Start
Apply supply voltage. All segments and decimal
points of the displays
T
MAX
and T are flashing.
The LED displays are being tested.
Operation
Actual value T (°C) below limit
value T
MAX
(°C)
Display T
MAX
Indication of the adjusted limit
Display T Indication of the actual value
Actual value T (°C) above limit
value T
MAX
(°C)
Display T
MAX
Indication of the adjusted limit
Display T Indication of the actual value and triggering of
an alarm.
Control unit NRS 1-40.1 / NRS 1-40.2 opens the
output contacts after the time delay has elapsed.
Test
The pushbutton for the TRV
5-40 on the control unit NRS
1-40.1 / NRS 1-40.2 must be
pressed and held down until
the test is finished.
Display T An increase in temperature is simulated and
the indicated actual value rises steadily. When
the adjusted limit value is exceeded, the control
unit NRS 1-40.1 / NRS 1-40.2 opens the output
contacts after the time delay has elapsed.
Indication of an error code
When an error occurs Display T Display switches between indication of error
code (E xx) and actual value T. The control unit
NRS 1-40.1 / NRS 40.2 opens instantaneously
the output contacts and the output of terminal
7,8 is energised/de-energised in a time-
controlled manner.
Start, Operation and Test
TRV 5-40
Fig. 6
Indication of
limit value
Indication of
actual value / error code
Vista de página 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 27 28

Comentários a estes Manuais

Sem comentários