23
Commissioning – continued –
Check switching functions - continued -
Electrode rod3 = timed pump control (fill control)
Electrode rod3 emerges Relay3 is energized, pump ON
LED3
illuminated
Electrode rod3 enters the
liquid
Relay3 is de-energized after a preset time delay
(0–30 sec.) = pump OFF
LED3 off
Relay 3 is de-energized too early or too late: Increase or decrease time delay with the aid of the
potentiometer and let electrode tip 3 emerge or enter the liquid again. Repeat the process until
you have found the correct switchpoint for the pump. If 30sec. time delay is not enough for filling
the boiler, please select the operation mode "on-off pump control".
Electrode rod3 = on-off pump control (fill control)
Set potentiometer for time delay to 0 sec.
Electrode rods2 and 3
exposed
Relay3 is energized, pump ON
LEDs2 and 3
illuminated
Electrode rod2 enters the
liquid
LED2 off
Electrode rod3 enters the
liquid
Relay3 is de-energized = pump OFF LED3 off
Electrode rods2 and 3 = on-off pump control (discharge control)
Set potentiometer for time delay to 0 sec.
Electrode rods2 and 3
submerged
Relay3 is energized, pump ON
LED2 off and
LED3
illuminated
Electrode rod3 emerges LED3 off
Electrode rod2 emerges Relay3 is de-energized = pump OFF
LED2
illuminated